Arc Interruption Performance of C4F7N-CO2 Mixture in a 126 Kv Disconnector

Boya Zhang,Ran Zhou,Kai Wang,Ze Guo,Xingwen Li,Minchuan Cao,Junwei Deng,Dibo Wang
DOI: https://doi.org/10.1109/tpwrd.2022.3210381
IF: 4.825
2023-01-01
IEEE Transactions on Power Delivery
Abstract:The C4F7N-CO2 mixture is considered the most promising alternative gas to SF6 in high voltage power apparatuses. This paper demonstrates the feasibility of using C4F7N-CO2 as an SF6 alternative to switch the current in a 126 kV disconnector. Firstly, the insulation performance of the mixture of C4F7N and CO2 was investigated and the appropriate fraction of the C4F7N-CO2 gas mixture was found to be 5% by taking the limitation of minimum operating temperature into account. Secondly, the arc interruption capability of C4F7N-CO2 and SF6 were compared. The arcing process of the bus-transfer current interruption was evaluated based on the magneto-hydro-dynamics (MHD) arc model. For the small inductive current interruption, the dielectric recovery properties were analyzed. In particular, the dielectric recovery strength of the C4F7N-CO2 during the post-arc phase was calculated based on the streamer inception criterion. Finally, the interruption experiments and type tests further verified the feasibility of the C4F7N-CO2 in the disconnector. The investigation in this paper demonstrates that the C4F7N-CO2 mixture can be used in the 126 kV disconnector to replace SF6.
What problem does this paper attempt to address?