Fast Simulation of Influence of Significant Height Difference and Multiple Branch Pipeline Structure on Indoor Unit Performance in VRF System

Yan Ziteng,Cao Haomin,Zhuang Dawei,Ding Guoliang,Oota Satoshi,Sato Masaaki,Suzuki Hideaki
DOI: https://doi.org/10.3969/j.issn.0253-4339.2023.01.059
2023-01-01
Abstract:There are significant height differences between outdoor and indoor units and many branches in the pipeline structure for variable refrigerant flow(VRF) systems in high-rise buildings, resulting in the performance degradation of indoor units. A simulation software is needed to determine the influence of these factors to improve the capabilities of such VRF indoor units. In this study, a distribution parameter model for the pipeline and a flow distribution model for the system based on fluid network theory were established to accurately reflect the flow characteristics of the refrigerant in the pipeline. A multi-zone separation model for the indoor unit heat exchanger and a fast pulse number calculation model for the indoor unit electronic expansion valve were also established to quickly reflect the operating status of indoor units. In addition, a hierarchical iterative solution algorithm was developed to improve the calculation speed of the software. These models were validated using existing data, and the results showed that the errors for each model were <12%, while the calculation time for the VRF system with a common structure was <1 min. Further more, the calculated example using the simulation software showed that the indoor unit performance decreased by 2.7%-11.9% when the height difference between the indoor and outdoor units increased by 20 m and by 0.4%-9.7% when the number of branches in the pipeline increased by one.
What problem does this paper attempt to address?