Dynamic Simulation of Variable Refrigerant Flowrate Air-Conditioning System

Shao Shuangquan,Liang Nan,Tian Changqing
DOI: https://doi.org/10.3969/j.issn.0253-4339.2011.01.016
2011-01-01
Abstract:In order to study the transient performance of variable refrigerant flowrate(VRF) air conditioning system,a dynamic simulation model is built based on simplified gas-liquid two-phase fluid network model.The numerical model consists of the dynamic lumped-parameter accumulator model,the moving-boundary condenser and evaporator model,steady-state compressor and electronic expansion valve model.And the numerical model is calculated by the software of Matlab and Simulink.The comparison with experimental data of a four-evaporator VRF system shows that the model can catch the dynamic trends of the VRF system with high accuracy,for example,the differences are about 1.0℃ of evaporating temperature,condensing temperature and superheating degree and the differences are less than 3.0℃ of discharging temperature.So,it can be used as an effective tool to analyze the transient performance and optimize the control strategy and algorithm of VRF system.
What problem does this paper attempt to address?