Impact of Wind Farm Integration on Relay Protection(2):Dfig-Based Wind Farm Electromagnetic Transient Equivalent Model
ZHANG Baohui,LI Guanghui,WANG Jin,HAO Zhiguo,ZHANG Jinhua,HUANG Renmou,WANG Xiaoli
DOI: https://doi.org/10.3969/j.issn.1006-6047.2013.02.001
2013-01-01
Abstract:A multi-machine equivalence scheme is proposed for the electromagnetic transient numerical simulation of large-scale DFIG-based wind farm.Since the short circuit current is related to the real-time rotor speed after the rotor Crowbar protection is put into operation during the short circuit fault of DFIG based wind generator,it is proposed that,the rotor speed just before the short circuit fault is taken as the classification index of DFIG-based wind generators.With the minimum value of the criterion function E after convergence as the criterion,the K-means clustering algorithm is applied to classify the generators with similar index.As there may be several types of DFIG-based wind generator in a group,the capacityweighted aggregation is applied to calculate the parameters of the equivalent wind power generators,i.e.the parameters of rotor motion equation,impedance,converter and its controller,and box-type transformer.The detailed model of a DFIG-based wind farm and its equivalent model are established on PSCAD/EMTDC platform and the simulative results show that,under the same fault condition,the fault current of equivalent model fits well that of the detailed model.