Experiments of Advanced High-Temperature Heat Pump Using Green Refrigerant R1233zd(E)

Jiatong Jiang,Bin Hu,Ruzhu Wang,Tianshu Ge,Hua Liu,Zhiping Zhang,Yu Zhou
DOI: https://doi.org/10.2139/ssrn.4098506
2022-01-01
SSRN Electronic Journal
Abstract:High-temperature heat pumps (HTHP) can play an extremely important role in reducing carbon emissions in industry heating. At the same time, heat pumps with low global warming potential (GWP) refrigerants need to be developed and promoted urgently, especially after the Kigali amendment entering into force. Therefore, an advanced high-temperature heat pump with green refrigerant R1233zd(E) is evaluated under 50 ℃ temperature lift conditions in this study. The advanced HTHP unit equipped with high-efficiency centrifugal compressor and enhanced heat exchangers was built to achieve the performance breakthrough. Control volume method of heat exchanger model was used in the simulation model of heat pump to optimize design of heat exchanger and heat transfer temperature difference from the perspective of the overall system. Experimental tests were conducted at working conditions of heat source temperature of 30~50 ℃ and output temperature of 60~100 ℃. At the condition of 50 ℃ heat source and supplying 100 ℃ hot water, heating capacity of 381kW and coefficient of performance (COP) of 3.67 are achieved, which is the highest efficiency compared with existing experimental results. The performance breakthrough of the advanced heat pump improves the HTHP technology and promotes the applications in industrial process heating.
What problem does this paper attempt to address?