Discharge Characteristics of Actual Winding Turn-to-turn Structure Inside Transformers under Oscillating Switching Impulse Voltage

R. Guo,Y. Sun,X. Zhang,J. Wu,J. Li
DOI: https://doi.org/10.1049/icp.2022.0243
2021-01-01
Abstract:In this work a real winding turn-to-turn model is designed and manufactured and the discharge characteristics of the model is studied. Both the standard switching impulse wave and the oscillating switching impulse wave are considered in the impulse withstand test, and the selected waves are in line with IEC 60060-3 standard. During the experiment, the partial discharge pulse sequence, breakdown voltage, and discharge time lag are obtained. The results show that as the voltage amplitude increases, the number of partial discharge pulses increases significantly. The partial discharge pulses are concentrated on the peak of the oscillation period under the oscillating switching impulse voltage. And the waveform oscillation has little effect on the breakdown characteristics of the winding, and the breakdown often occurs at the peak of the first cycle. This paper provides experimental support for studying the influence of oscillating waves and double-exponential waves on the insulation characteristics of transformers.
What problem does this paper attempt to address?