Natural Ventilation Performance of Solar Chimney with and Without Earth-Air Heat Exchanger During Transition Seasons

Tianhe Long,Ningjing Zhao,Wuyan Li,Shen Wei,Yongcai Li,Jun Lu,Sheng Huang,Zhenyong Qiao
DOI: https://doi.org/10.1016/j.energy.2022.123818
IF: 9
2022-01-01
Energy
Abstract:This study experimentally investigates the natural ventilation performance of a solar chimney (SC) integrated with an earth-air heat exchanger (EAHE) during the transition seasons. The experiment was conducted in a comparative manner under three operating modes: Mode A: SC operating with EAHE with the window closed; Mode B: SC operating with an open window with the same opening area as the cross-sectional area of the EAHE pipe, with the EAHE closed; Mode C: the operating mechanism was the same as that of Mode B with the window opening area doubled. The results showed that 24 h of natural ventilation was achieved for the three operating modes. However, the nocturnal ventilation driving force for Mode A was the heating effect of the subsoil, while that for Modes B and C was the heat released from the thermal mass. The average daytime and nocturnal airflow rates for Modes A, B, and C were 209 m(3)/h and 139 m(3)/h, 286 m(3)/h and 87 m(3)/h, and 340 m(3)/h and 80 m(3)/h, respectively. The 24 h overall heating and cooling capacities of the EAHE for Mode A were 19474 kJ and 2179 kJ, respectively. The SCEAHE system had an advantage in preserving acceptable indoor thermal comfort with a diurnal indoor temperature variation in the range 19.7-22.7 degrees C. (C) 2022 Elsevier Ltd. All rights reserved.