Experimental Investigations and Numerical Analysis of Solar Chimney for Building Ventilation

Xinyu ZHA,Menghao QIN
DOI: https://doi.org/10.13614/j.cnki.11-1962/tu.2017.04.02
2017-01-01
Building Science
Abstract:Based on experimental investigations of a solar chimney in East China,the results of theoretical calculation and numerical simulation were compared.The results show that the actual measurement of ventilation rate is generally lower than the theoretical value.Intensity of solar radiation on the vertical surface in 9∶15 ~ 13∶15 period of the day was 5 ~ 600 W/m2,and the measured ventilation rate was 0.02 ~ 0.45 m/s.This study suggests the discharge coefficient of solar chimney be 0.51 in project.Numerical simulation indicates that the size of a solar chimney has an influence on natural ventilation,i.e.ventilation rate grows when the height or width of the solar chimney increase.For the vertical type of solar chimney,it has the best height-to-width ratio of 0.3 ~ 0.4 to achieve a great ventilation rate.
What problem does this paper attempt to address?