Study On The Characteristics Of Indoor Inhalable Particle Distribution In Underfloor Air Supply System

Li Can,Li Nianping,Wang Meixia,Yao Guocai
2007-01-01
Abstract:To investigate the indoor environment in underfloor air supply system, the influence of factors affecting the level of indoor inhalable particle concentration (PM10), which is one of the important criteria for indoor environment, were analyzed, then a model of PM10 level was developed based on mass balance equation. The contributions of ventilation volume, the initial PM10 concentration, infiltration, resuspension rate for PM10 concentration were studies theoretically and experimentally. The particle size distribution was measured also. Experiments observation indicates that the model of the particle mass concentration is effective. The PM10 concentration decreases with the air change rate increasing, and with the resuspention rate decreasing. The historical concentration of particle has no apparently influence to the indoor concentration on steady state. The particle size distribution showed in experiment that the relation between the log-log plot of cumulative frequency and diameter is linear relation. Entrainment of the particles in surface due to supply air is weak under a condition without human activities. However, with human light activities, the suspended particle concentration for larger particles (more than 1 mu m) ca significantly increase.