Effect of Flow Imbalance on the Operational Performance of the KSTAR PF1UL Magnets

Hyun Jung Lee,Yong Chu,Kwang Pyo Kim,Hyun Wook Kim,Kabrai Park
DOI: https://doi.org/10.1016/j.fusengdes.2021.112770
IF: 1.905
2021-01-01
Fusion Engineering and Design
Abstract:The installation of a cryogenic circuit for a large-scale superconducting device such as a tokamak is quite complex. In the KSTAR tokamak, five cryogenic circuits are utilized to cool each type of the component (e.g., toroidal field magnets, poloidal field magnets, structures current leads, thermal shield, bus lines) independently. The circuit for the poloidal field magnets branches into hundreds of cooling channels. And five cryogenic valves control the flow rates according to the length of the cooling path. Ten cooling paths are arranged in parallel for cooling of the PF1 upper and lower magnets. The pressure drop is adjusted by a cryogenic valve with maintenance by a supercritical helium circulator. Although the flow rate should be uniform among the cooling channels but the flow imbalances was observed during flow tests at an individual magnets test. The flow rate should be uniform among the cooling channels but the flow imbalances observed during flow tests at an individual magnets test. The measured imbalance was around 10% between the KSTAR PF1 upper and lower magnets. To investigate the effects of the flow imbalance on the magnet temperature, a model of the PF1 upper and lower magnets system is developed using the SUPERMAGNET code. The maximum temperature trends are investigated depending on the flow imbalance.