Movable Membrane-Based Separation System with High SF6 Retention for Large-Scale Gas-Insulated Transmission Lines During Maintenance

Qing Li,Minggang Guo,Gaohong He,Xiaoming Yan,Wenji Zheng,Yan Dai,Xuehua Ruan
DOI: https://doi.org/10.1016/j.seppur.2021.118438
IF: 8.6
2021-01-01
Separation and Purification Technology
Abstract:Large-scale gas-insulated transmission lines based on N-2/SF6 mixture, subject to the cramped culvert space and the strict environmental standard, requires high efficient and compact separation systems during equipment maintenance. In this work, membrane separation system with adequate SF6 retention (377 ppmv in the discharged stream), competent separation capacity (50 Nm(3)/h) and compact footprint (moved in cramped culverts narrower than 4.0 m) was customized successfully. Commercial polyimide asymmetric membrane modules were selected after systematic tests. The specific operation under elevated temperature was attempted to reinforce permeation ability and selectivity simultaneously. The test sustained by 1050 h revealed that these modules possessed favorable long-term stability under 100 degrees C and 2.0 MPaG. In this instance, their N-2 permeance is about 6.4 GPU, and N-2/SF6 selectivity is about 104, respectively. In comparison with the common mode at 25 degrees C, the temperature-elevated operation mode can enhance N-2 permeance by 2.3 times and selectivity by 1.8 times, highly advantageous to downsize the separation system. On the basis, the four-membrane-block process framework was customized to construct the practicable system for N-2/SF6 separation. The composition equilibrium curve, analogous to the equilibrium curve for distillation, was proposed for process framework schematization. After equipment size assessment, it is concluded that this separation system for large-scale underground gas-insulated transmission lines could be assembled into two movable platforms (330 cm x 180 cm, and 240 cm x 180 cm) and transported conveniently in the cramped culverts.
What problem does this paper attempt to address?