Performance prediction model for chiller with variable water flow and its experiment validation

Chuyao Jiang,Caihua Liang,Xiaosong Zhang
DOI: https://doi.org/10.3969/j.issn.1001-0505.2014.02.014
2014-01-01
Abstract:To simulate existing chiller with variable water flow accurately under the condition of con-figuration parameter absence,a modeling method which makes unknown parameters lumped and ob-tains model parameters based on measured data of chiller is proposed.A performance prediction model for chiller with variable water flow is developed,and an experimental device is built up to ob-tain the parameters of the model and make a comparison on the performance of chiller between simu-lation and experiment.The results show that by this modeling method,the parameters of the model are easy to gain,and the performance prediction accuracy of the model is high.The relative errors of performance parameters such as cooling capacity and COP (coefficient of performance)between simulation and experiment are within 10%,and the variation of the performance of chiller with varia-ble water flow can be represented accurately.When chilled water flow decreases from 100%to 42.8%of the rated flow rate,cooling capacity decreases 8.6%and COP decreases 8.8%.When cooling wa-ter flow decreases from 100%to 24.2%of the rated flow rate,cooling capacity decreases 1 .8%and COP decreases 14.8%.The results can provide evidence for the optimal operation of chiller.
What problem does this paper attempt to address?