Energy-efficiency Performance with Variable Air-conditioning Water Flow Rate

JIANG Xiao-qiang,LONG Wei-ding,WANG Min,Xie Ai-xia
DOI: https://doi.org/10.3969/j.issn.1005-0329.2010.03.016
2010-01-01
Abstract:For reduce energy consumption and improve operating efficiency of air-conditioning,the influence of variable flow rate of chilled water and cooling water on the chilled COP and the energy consumption was analyszed.The maximum cooling load was predicted by DOE-2 software and built the chiller and pump models for simulate.The chiller COP and energy consumption of chiller and pump were computed utilizing TRNSYS.Result showed the chiller COP have decrease 8.04% and 9.96% when the chilled water and cooling water flow rate from 100% to 50%,while the total energy consumption has reduced 15.79% and 13.56% relatively fixed flow rate system.This shows that both the cooling water flow or variable flow chilled water chillers are reducing the value of the COP,but it also can reduce overall system energy consumption;the technology of variable chilled water flow rate will more high-efficiency than variable cooling water flow rate and the scope of variable cooling water flow should not be too large.