Research on a Plan of Free Cooling Operation Control for the Efficiency Improvement of a Water-Side Economizer

Yu-Jin Kim,Kwang-Hee Kim,Ju-Wan Ha,Young-Hak Song
DOI: https://doi.org/10.3390/en17122804
IF: 3.2
2024-06-08
Energies
Abstract:The energy reduction in chillers has been considered an important factor in the energy efficiency improvements of cooling systems, and water-side free cooling is regarded as the key of chiller free cooling technology. Therefore, this research aims to develop a control methodology for the extension of the free cooling operation time in order to improve the efficiency of water cooling-type chillers based on a WSE (water-side economizer) system for a data center and review the proper control conditions through an energy usage analysis of the entire system. The suggested methodology is an increase in the chilled water supply and return temperature according to the increase in the CARH (Computer Room Air Handler) fan air flow and a decrease in the chilled water flow. A case study was conducted according to the application of control through an EnergyPlus simulation. The results of the simulation show that energy usage was reduced by 8.1% under 120% CRAH fan capacity and 100% chilled water flow conditions. When applying the control plan, the free cooling period was extended according to the increased CRAH fan capacity and decreased chilled water flow. However, the increase in the CRAH fan energy must be considered. Also, in the case of a reduction in the chilled water flow, it is necessary to consider a point that can guarantee the cooling treatment heat rate in the heat exchanger.
energy & fuels
What problem does this paper attempt to address?
### Problems the Paper Aims to Solve This paper aims to address the issue of increasing chilled water temperature in data center cooling systems and to extend the operation time of free cooling through control methods, thereby improving the efficiency of Water-Side Economizer (WSE) systems. #### Specific Objectives: 1. **Develop Control Methods**: Propose a control method to extend the operation time of free cooling, thereby improving the efficiency of water-cooled chillers based on WSE systems. 2. **Analyze Control Conditions**: Review appropriate control conditions through an energy usage analysis of the entire system. 3. **Increase Chilled Water Supply and Return Temperature**: Increase the chilled water supply and return temperature based on the increase in airflow of the Computer Room Air Handler (CRAH) fans and the reduction in chilled water flow. #### Research Scope: - **Detailed Study of Chilled Water Temperature Changes**: Before establishing the control process, a detailed study was conducted on the impact of CRAH fan airflow and chilled water flow on chilled water temperature changes. - **Simulation Analysis**: Annual simulations were conducted using the EnergyPlus dynamic energy simulation program to analyze the energy impact of the WSE system and to analyze the extension of the free cooling operation period. Through the above research, the paper aims to develop a set of control strategies to maximize the free cooling operation time of the WSE system and reduce the energy consumption of the entire system.