Abstract:Cabinet backboard air conditioner has a good application prospect in increasing room utilization ratio, energy saving and eliminating the local hot spot, whether the normal operation of fans is the key to perform its performance. This paper aimed to make simulation analysis for the fan malfunctions and emergency methods, which setting three malfunction points on the upper, middle and lower backboard evaporator with 10 double-row fans. The results show that fan malfunction position is higher, the temperature rising of local hot spots is larger; fan malfunction can cause cooling capacity decreasing, but the capacity decline has not obvious relationship with fan malfunction position; the more air volume of fans around the malfunction fan increase, the better the cooling effect will be made for the whole cabinet.