ENHANCING UNIFORMITY OF AIRFLOW AND TEMPERATURE DISTRIBUTION FOR PRODUCE COOLING IN A COLD ROOM BASED ON FIELD SYNERGY PRINCIPLE

Guan-Bang Wang,Xin-Rong Zhang
DOI: https://doi.org/10.1615/jenhheattransf.2021037896
2021-01-01
Abstract:Additional axial fans have been empirically used to enhance the airflow in a cold room for higher uniformity of convective heat transfer. The present study investigates the guiding mechanism of the holistic optimization for airflow and heat transfer as well as the arrangement of axial fans in a cold room. Field synergy principle (FSP) is employed to obtain the theoretically optimal airflow organization for the enhanced convective heat transfer based on the solution of governing equations derived by the variational method. The practical arrangement of axial fans is then proposed to achieve the flow field indicated by FSP, and a numerical simulation is conducted to investigate the effects of operating conditions. The results of FSP indicate airflow enhancement particularly in the gaps between produce bins, while enhanced airflow is generated by axial fans in the lengthwise gap between two lines of produce bins for practical applications. The use of these fans results in reduced temperature heterogeneity in terms of the highest deviation between the maximum and minimum produce temperature in the centers of different bins. The hot spots are weakened with smaller regions and lower produce temperature by increasing operating angular velocity of axial fans, while the reduction of these fans results in both the alleviation and aggravation of hot spots at different positions. This study shows the effectiveness of FSP to guide the optimization of airflow organization in a cold room and provides a practical strategy to improve cooling uniformity.
What problem does this paper attempt to address?