Numerical simulation of the smoke propagation mechanism and fire control methods for subway tunnel

Yusheng HOU,Yanfeng LI,Yiran WANG,Yao LIU,Ning DU
DOI: https://doi.org/10.3969/j.issn.2095-2783.2016.07.010
2016-01-01
Abstract:To investigate the effect of smoke exhaust fan operation time in smoke control ,numerical simulation was used to inves‐tigate fire scenarios in a circular shield subway tunnel with inner diameter of 5 .5 m .Temperature fields and the position of maxi‐mum temperature in the subway tunnel were calculated for fire with heat release rate of 5 ,7 .5 and 10 MW ,respectively .In addi‐tion ,the effect of delay on start time of exhaust fan on smoke propagation is also evaluated .Results showed that the maximum smoke temperature under ceiling was larger with the increase in heat release rate of fire .The critical wind velocity has a weaker influence on the maximum temperature field with the increase of fire load .Starting delay of exhaust fan would damage the stabili‐ty of smoke layer .Smoke layer would descend to the train carriage and the temperature of air near train would increase .This effect was harmful to passenger safety evacuation .