Project of Isolating Fault-Pipes in Loop Heating Network and Its Hydraulic Condition

WANG Xiao-xia,ZOU Ping-hua,TAN Yu-fei
DOI: https://doi.org/10.3321/j.issn:0367-6234.2005.04.013
2005-01-01
Abstract:A hydraulic analytical method of heating system faulty condition is presented based on dimensional network, Two heat consumer fault instances non adjustment and limit quantity of heat-supply are discussed. Two hydraulic conditions of loop pipe at the same faulty condition are simulated simultaneously closing supply valve and return valve ( projectⅠ) by and closing supply valve or return valve ( project Ⅱ). The results indicate that both projects can make heat consumers produce maladjustment while heat consumers do not adjust, but maladjustment extent of project II is smaller than that of project Ⅰ. The maximum system limitation heating coefficient of project Ⅱ is bigger than that of project Ⅰunder limit quantity of heat-supply condition. Hence, project Ⅱ can reduce heating network cost when assuring reliability.