Apply member loads to calculate wind load shape coefficient of angle-made-transmission tower

Wen-juan LOU,Hong-chao LIANG,Rong BIAN
DOI: https://doi.org/10.3785/j.issn.1008-973X.2018.09.001
2018-01-01
Abstract:JEC assembly method and Simon assembly method were introduced; transmission tower section model... wind tunnel measuring pressure test at turbulence intensity of 14% was conducted; the pressure coefficient at both upstream and downstream of the main members, oblique members and auxiliary members were obtained. Results show that, when applying JEC assembly method, the reduction factor of slenderness ratio is about 15% smaller than experimental result, and the wind load reduction coefficient of leeward members are about 4% larger.While applying Simon assembly method, the wind load reduction coefficient of leeward members agree well with the test, but the shape coefficients of the members at upstream are about 10% smaller than the experimental results. Based on wind tunnel test results, a modified assembly method was proposed by improving the accuracy of parameters recommend by JEC. The shape coefficient calculated by modified assembly method is in good agreement with the experiment result and the American standard.
What problem does this paper attempt to address?