Effect of sample size on transient measurement of water vapor diffusion coefficient

Shuai-qi TIAN,Qing-yu ZHANG,Ke WANG,Li-wu FAN,Zi-tao YU,Jian GE
DOI: https://doi.org/10.3785/j.issn.1008-973X.2018.11.005
2018-01-01
Abstract:The transient experiments of water vapor diffusion coefficient in the lengthwise direction of B04 autoclave aerated concrete (AAC) samples were performed to reveal the effect of sample size on transient measurement of water vapor diffusion coefficient. The axial sample lengths were 120, 150, 200 and 250 mm, respectively, while maintaining a constant cross-sectional area of 50 mm×50 mm. Results of steady-state and transient measurements were compared. Results showed that the transient results increased along with the decrease of the samples’ length. The transient results of the 120 mm sample were slightly higher than the steady-state measurements while the maximum deviation was less than 10% when the relative humidity was higher than 50%, and the measurement time was 24 h. The transient results of the 150 mm sample had the best agreement with the steady-state results with an overall deviation of less than 13%, and the measurement time was 36 h. The transient results of 200 mm and 250 mm samples were apparently lower than the steady-state results, while the maximum deviation was greater than 25%, and the measurement time was longer than 60 h. According to the results, the sample length of 150 mm is recommended for the transient measurements on the water vapor diffusion coefficient of this type of AAC.