Experimental Investigation for Low-concentration Liquid Desiccant Regeneration with Utilization of Condensation Heat

Taiye Zeng,Xiaosong Zhang,Yao Chen
DOI: https://doi.org/10.3969/j.issn.0253-4339.2018.01.076
2018-01-01
Abstract:To investigate the heat and mass transfer effects on the regeneration process using condensation heat,experiments were performed in a hybrid air-conditioning system using low-concentration LiCl solution as the liquid desiccant.The regeneration rate and utilization ratio of condensation heat were regarded as evaluation criteria of regeneration performance.The effects of the important operating parameters on the system performance were analyzed experimentally.The results show that the air and solution mass flow rate and inlet temperature have a positive impact on the performance of regeneration.Under typical summer conditions,as the solution concentration increases from 21.20% to 24.91%,the utilization rate of condensation heat fluctuates between 0.416 and 0.507;the utilization rate of condensation heat would increase if the solution concentration was reduced.Finally,empirical correlations coupling the heat and mass transfer coefficients are presented.The experimental results provide reliable data for further analysis of using condensation heat efficiently for the solution regeneration process.