Analysis of Influence of Rolling on Heat Transfer Characteristics of Two-phase Falling Film Flow of Refrigerant outside Horizontal Tubes

Jian-rui LI,Jie CHEN,Hui PU,En-dao LI,Guo-liang DING,Hai-tao HU,Da-wei ZHUANG
DOI: https://doi.org/10.3969/j.issn.2095-4468.2016.05.104
2016-01-01
Abstract:To avoid the performance decrease of coil-wound heater exchanger under offshore conditions, the falling film evaporation process outside the tubes is simulated under different rolling conditions, and the influence of rolling angle and frequency on heat transfer characteristics is analyzed. The results show that, the heat transfer coefficient is decreased by 27% when the rolling angle is 9° and the vapor quality is 0.05; the heat transfer characteristic is slightly enhanced when the rolling frequency is low;it is more sensitive for the rolling influence when vapor quality is 0.2, and the heat transfer coefficient is decreased by 11%when the rolling angle is 3°.
What problem does this paper attempt to address?