Abstract:The effect of protecting mesh of air conditioner outdoor unit on aero-acoustic noise is studied with experimental method. Test result shows that, if the frequency of air flow wake vortices behind protecting mesh is near 1000Hz, the aero-acoustic noise is rapidly increased. So, during design of air conditioner outdoor unit, the matching about fan exit flow velocity and steel diameter of protecting mesh is an important method for decreasing noise.