Experimental Research on Static Scale and Corrosion Inhibition Using Low Frequency Electromagnetic Treatment of Reclaimed Water

CHI Jin-bao,ZHANG Xue-feng,CANG Da-qiang,ZHAO Min,CHANG Rui-qing
DOI: https://doi.org/10.3321/j.issn:0449-749x.2009.06.020
2009-01-01
Abstract:According to scaling and corrosion problems during operation process of circulating cooling water,static water quality stabilization experiment was conducted on treatment reclaimed water with low frequency gradient electromagnetic field.After optimizing the electromagnetic operation parameters by orthogonal experiment,the scale inhibiting rate came to 21.46% and the corrosion inhibition came to 12.31% under disposable electromagnetic treatment.These two values could be improved to 35.30% and 17.50% respectively,after multiple circulating electromagnetic treatments for 2.0 h.By using SEM(Scanning Electronic Microscope)and XRD(X-Ray Diffraction),electromagnetic treatment could change structural morphology of CaCO 3 crystal,promote formatting of compact γ-Fe 2O 3 oxide film on iron surface,which is against corrosion.
What problem does this paper attempt to address?