Study on measurement technology of impulse dispersing current in tower grounding device

Zhou Lijun,Mei Cheng,Gu Weifu,Xu Han,Wang Pengcheng
DOI: https://doi.org/10.19650/j.cnki.cjsi.J1804219
2019-01-01
Abstract:The effectiveness of dispersing current under lightning impulse on equipment and biology has been widely recognized. At present, there is no effective measurement of impulse dispersing current near tower grounding device. Therefore, the measurement technology is studied in this paper. Firstly, a device for measuring impulse dispersing current in the ground is made by using flat electrode structure and the calculation method of the current density in the ground is proposed. Then, a test platform is built to determine the appropriate device size. To meet the measurement requirements, the space of the electrode plate should be controlled at 0.01~0.02 m. The length and the width of the electrode plate should be controlled at 0.05~0.1 m. Finally, the measurement accuracy of the device is verified by simulation test. The absolute error of the device is less than 10 A/m2. The device has been applied to the pilot project in Foshan City, Guangdong province.
What problem does this paper attempt to address?