The study on the fault current characteristics of doubly fed induction generator with low-voltage ride-through control strategy

Xiangping Kong,Zhe Zhang,Yubo Yuan
DOI: https://doi.org/10.3969/j.issn.1001-1390.2016.20.012
2016-01-01
Abstract:Under conditions of non-severe fault , the depth of voltage dip is not very large .With the application of low-voltage ride-through control strategy , the rotor windings of doubly fed induction generator ( DFIG) are still excited by the AC/DC/AC converter.Hence, the fault current characteristics of DFIG under conditions of non-severe fault are decided by the response of the AC/DC/AC converter .Aimed at it , the dynamic response characteristics of rotor-side converter ( RSC) with low-voltage ride-through control strategy are analyzed , and the generalized calculation model of the rotor fault current is obtained .Based on it , the stator fault current characteristics of DFIG in condition of non-se-vere fault are studied .Meanwhile , the unified analytical expressions of the stator fault current are established .Final-ly, the digital simulation examples in PSCAD/EMTDC demonstrate the correctness of the theoretical analysis results .