Fault Currents of the Doubly Fed Induction Generator with Constant AC Excitation

ZHANG Lu-hua,GUO Jia-hu,CAI Xu,CAO Yun-feng,CHENG Meng-zeng
DOI: https://doi.org/10.16183/j.cnki.jsjtu.2010.07.026
2010-01-01
Shanghai Jiaotong Daxue Xuebao/Journal of Shanghai Jiaotong University
Abstract:This paper systematically analyzed the dynamic responses of doubly fed induction generator (DFIG) stator and rotor currents when three-phase short circuit occurs at stator terminals, and also presented a new approach in which the DFIG under fault condition is equivalent to a rotor excited induction machine running in a steady state and a squirrel-cage induction machine subjected to three-phase short circuit, to get the fault currents. Space vector analysis was introduced to get the analytical expression of fault currents. The maximum rotor and stator short circuit currents as well as the times when they appear were proposed. Furthermore, main components of the short circuit currents and their relations were presented. Finally, all above results are validated in Matlab/Simulink.
What problem does this paper attempt to address?