Simulative and Experimental Studies on the Effect of Superheat Degree on the Refrigeration System Performance

LIANG Cai-hua,ZHANG Xiao-song,XU Guo-ying
DOI: https://doi.org/10.3969/j.issn.1005-0329.2005.09.011
2005-01-01
Abstract:Model simulation and experiments are carried out to investigate the effect of superheat degree on the performance of Air Cooled Screw Heat Pump.Both simulative and experimental results reveal the relations between superheat degree and performance characteristics.Furthermore,The experimental result shows that change of superheat degree at the outlet of the evaporator from 10℃ to 2℃ will cause 13.4% increase in cooling capacity and 9.3% increase in COP,but only 4% increase in power consumption.It is easily obtained that using electronic expansion valve to decrease the superheat degree could improve the system performance remarkably.
What problem does this paper attempt to address?