Theoretical Study on Capturing the Separation Interface of Out-of-step Based on Reactive Power

GAO Peng,WANG Jian-quan,ZHOU Wen-ping,ZOU Yu
DOI: https://doi.org/10.3321/j.issn:1000-1026.2005.05.004
2005-01-01
Abstract:The characteristics of electrical parameters of separation interface are discussed when an equivalent two-machine power system is out-of-step. While a multi-machine system is out-of-step and splits into two coherent groups, the separation interface, generally composed of several tie-lines, will disconnect the whole transmission network into two coherent electrical islands. The characteristics of the separation interface tie-lines are as follows. First, the active power flow crosses zero and oscillates periodically. Secondly, there is one point, the center of out-of-step, existing in the interconnector whose voltage amplitude change is the largest when compared with those of other points, viz. a large voltage gradient in separation interface occurs during the course of out-of-step. Thirdly, reactive power flows from both sides to the interior of the separation interface. The integral value of reactive power in one period of out-of-step reflects the characteristics of separation interface by adopting the first characteristic above. Thus the reactive power based method of capturing separation interface is presented.
What problem does this paper attempt to address?