IMPROVEMENT OF THE APPARENT IMPEDANCE ANGLE SEPARATION CRITERION

高鹏,王建全,周文平
DOI: https://doi.org/10.3321/j.issn:1000-1026.2004.24.009
2004-01-01
Abstract:Based on the study on the characteristics of the changes of tie-line power flow and apparent impedance angle of out-of-step equivalent two-machine power system, the apparent impedance angle separation criterion which cannot get the actual number of swings was proposed. That is because system loses its synchronism quickly due to severe accident and becomes asynchronous in excess electromagnetic transient state. A method of calculating the number of swing is proposed by setting a proper threshold to compute the number of the active power zero-crossing. Simulation studies are given and the field experiences proved that the method can detect the correct number of short period swings.