Dead Time Effect in the Parallel Inverters

ZHANG Yu,CHEN Xi-kun,KANG Yong,CHEN Jian
DOI: https://doi.org/10.3969/j.issn.1000-100x.2005.05.035
IF: 5.967
2005-01-01
IEEE Transactions on Power Electronics
Abstract:This paper analyzes the circulation currents caused by dead times,which were significant in high power inverters and varied with the quantity and power factor of the load.Because the dead times in high power inverters are always large,when it realized by the hardware,the discrepancy of dead times are also large.On the other hand,the filter inductances and output impedances are normally small in high power inverters,these make the discrepancy of dead times result in large circulating currents.The circulating currents caused by the discrepancy of the dead times include plenty low order harmonics and can hardly be eliminated by the load share regulators.This paper analyzes the mechanism of the dead time effecting on circulation currents.The simulation and experiment based on 20kVA inverters indicated that 2μs difference in dead times will cause 30A circulation currents in magnitude and lead to bad aftermath.So the the discrepancy of dead times in high power inverters should be avoided.