Soil Structural Model Analysis of Wudaoliang and Tuotuohe Substations for 110kv Power Transmission Engineering of Qinghai-Tibet Railway
HE Jin-liang,KANG Peng,ZENG Rong,ZHANG Bo,HUA Pu-xiao
DOI: https://doi.org/10.3321/j.issn:1000-3673.2006.04.012
2006-01-01
Abstract:The 110kV Tuotuohe and Wudaoliang substations supplying power for Qinghai-Tibet railway locate in arctic-alpine permafrost area, so it is very important for the construction of substation how to design grounding system in arctic-alpine permafrost area. By means of measuring the insulation withstand properties of secondary cables and devices, it is proposed that the ground potential rise can be increased to 5kV. Applying the numerical analysis method of electromagnetic field to electrical parameter calculation of grounding system in layered soil, various feasible design schemes for grounding system in arctic-alpine permafrost area are analyzed and compared, the arrangement regularity of deeply-buried vertical grounding electrodes, the burial depth of horizontal grounding grid, the influence of grounding system's optimal arrangement on grounding resistance, touch voltage and step voltage of grounding system are researched. Eventually the grounding system design scheme for Tuotuohe and Wudaoliang substations is obtained. At the same time, the regular patterns of grounding system design in arctic-alpine permafrost area are summarized and induced.