INVESTIGATIONS ON SWITCHING IDLE POWER TRANSFORMER WITH PHYSING VACUUM CIRCUIT BREAKERS

DING Fu-hua,ZOU Ji-yan,FANG Chun-en,DUAN Xiong-ying
DOI: https://doi.org/10.3321/j.issn:0258-8013.2005.03.017
2005-01-01
Abstract:The inrush currents generated by the energization of unloaded transformer have unfavorable effects such as protective relay misoperation, imposed sever mechanical stresses on the transformer windings and reduced power quality of the system. Controlled transformer switching can potentially eliminate these inrush currents and the optimal instant to energize the transformer is when the “prospective” flux is equal to the residual flux. This paper analyses the transient process of energizing unloaded transformer and introduces several strategies for controlled energization. Both simulation and experimental results in laboratory indicate that phase-control vacuum circuit breakers with permanent magnetic actuator can be used to realize the controlled switching.
What problem does this paper attempt to address?