Review in Application of High Voltage Composite Insulator and Its Ageing State

Qi Chen
DOI: https://doi.org/10.16790/j.cnki.1009-9239.im.2016.04.002
2016-01-01
Abstract:The development and application situation of composite insulator was reviewed. The ageing mechanism and analysis methods of composite insulator in service were introduced. The ageing evaluation methods of composite insulator, including thermal stimulation depolarization current (TSDC), Fourier trans-form infrared spectrum (FTIR), nuclear magnetic resonance (NRM), and positron annihilation lifetime spec-tra (PALS), were elaborated mainly, and the relative research results were anlyzed. The TSDC, FTIR, and NMR could evaluate the ageing degree of composite insulator from the variation of trap depth, chemical groups, and relaxation time. The PALS is a new microstructure detection method, which can measure the variation of free volume of composite insulator before and after ageing accurately. So the PALS could be used to deeply understand the ageing process of composite insulator in microcosmic scale through combin-ing the above three methods in later studies.
What problem does this paper attempt to address?