Design of Double Needles Defect Model in Oil Immersed Inverted Current Transformer and Its Partial Discharge Characteristic

Kui Ma,Xutao Wu,Wei Ma,Bo Gao,Bo Wu,Rui Zhang
DOI: https://doi.org/10.16790/j.cnki.1009-9239.im.2015.08.012
2015-01-01
Abstract:Metallic protrusion on the electrode surface is a typical insulation defect of oil immersed inverted current transformer. In order to know its partial discharge (PD) characteristics, a double needles defect model is made in the laboratory to simulate the metallic protrusion defect, and its electric field distribution was calculated by ANSYS finite element software. According to the calculation results, two defects were selected to test their PD characteristics by PDcheck and Rogowski coil. The results show that the PD pulses can be divided into two kinds according to the PD magnitude, one kind of pulses represents the partial discharge happened in oil, while the other kind of pulses represent the partial discharge happened in air gaps of oil. When the distance between two needles increases to 30 mm, the PD pulses distribute randomly in the whole cycle. These pulses can be hardly separated from noise signals in the phase-resolved partial discharge (PRPD) spectra.
What problem does this paper attempt to address?