Structural Optimization of Condensers with Refrigerant Blends Based on Heat Transfer and Pressure Drop Coupling

Fang WANG,Xian-ping ZHANG,Xiao-wei FAN,Zhi-wei LIAN,Di XU,Yi-ke FU
DOI: https://doi.org/10.3969/j.issn.1003-9015.2016.00.040
2017-01-01
Abstract:A tube length optimization model based on minimum entropy production was proposed for R744/R290(20/80) and R125/R290(25/75) counter-flow condensers considering coupling of heat transfer and pressure drop. The concept of performance potential evaluation index(PEI) and Total Temperature Penalization(TTP) for mixed refrigerant condensation proposed by Cavallini was used, and the relationship between PEI and heat transfer coefficient was obtained. The effects of condensing temperature, tube diameter and passive pressure drop on optimal tube length were analyzed. The results indicate that the saturation temperature drop value of refrigerants is 0.6 times of that of heat transfer temperature difference between refrigerant and wall. The higher pressure refrigerant (lower critical temperature) R744/R290 (20/80) has lower PEI value and better performance than others, and smaller tube diameter condenser has shorter optimal tube length. The optimal tube length increases with the increase of condensing temperature, while it decreases with the increase of pressure drop.
What problem does this paper attempt to address?