Field measurement of natural ventilation performance of Shanghai Zhongxin Square

Wenting Ding,Junsheng Du,Shu Nagase,Rui Hu,Yiqun Pan
2014-01-01
Abstract:Presents the natural ventilation design for Shanghai Zhongxin Square,simulation of ventilation performance during the design phases and field measurements after the building completion.The simulation results show that air change rate of the calculated space can reach to 0.8 to 3.1 h-1 during transition season.The field measurement results show that indoor air change rate can reach to 1.0 to 5.6 h-1 when all natural ventilation openings are opened,which can basically meet the minimum fresh air requirement of indoor occupants.Results of the field measurements are close to simulation results.Natural ventilation performance functions well as design expected.