Optimization of Disinfection Technology and Its Application in Water Treatment Plant

刘丽君,焦中志,刘文君,张金松,刘茜,陈忠林
DOI: https://doi.org/10.3321/j.issn:1000-4602.2005.01.002
2005-01-01
Abstract:According to the objectives on the saving of disinfectant and reduction of DBPs in the demonstration project of Bijiashan Water Plant, measures were taken for improving chemical feeding method and optimization of clear water tank configuration. The result shows that improvement of feeding method can decrease chlorine by 20% and save energy about 15%; modification of clear water configuration can increase detention time of disinfectant in water, and thus lowering the concentration of disinfectant without reducing disinfection efficiency. The t_(10)/T value is increased by 42%, 21%, and 29% respectively in the three tanks with flow pattern improved greatly.
What problem does this paper attempt to address?