Experimental study on low-pressure water mist for protection of high-rack storage

Yufang LIU,Bin YAO,Wenwei WANG,Ya SHU
DOI: https://doi.org/10.3969/j.issn.1004-5309.2015.03.04
2015-01-01
Fire Safety Science
Abstract:Due to special structure traits and storage characteristics,high-rack storage involves higher fire risk compared to ordinary warehouse. Currently, ESFR sprinkler is the primary choice for high-rack storage while water mist is rarely considered.By conducting experiment of low pressure water mist for extinguishing high-rack storage fire,the working pressure of sprinkler,ignition time,spray start time,flame extinction time and the quantity of goods burned were recorded,and the temperature,heat radiation and sprinkler discharge rate were analyzed.The results illustrate that low pressure water mist protects high-rack storage very well under the situation of the limited height of storage and shelf with less water consumption and less water damage compared to other sprinkler systems.
What problem does this paper attempt to address?