Abstract:Gambit was used to establish the blast furnace slag wool pipe composite insulation structure model and mesh was divided , in the FLUENT simulation software, the heat transfer process of the pipe composite insulation structure was numerical simulated in order to investigate the temperature field of pipe insulation under different temperatures and different external conditions.The results show that the suitable thickness of insulation layer of the pipe with 57 mm, 216 mm outside diameter are about 22 mm and 38 mm respectively.Simulation of one hundred meters long pipeline shows that the outlet temperature calculated were above 94 ℃ in various conditions, and surface temperatures insulation are lower than 40 ℃.At the same time, the results verify that the thermal insulation structure in the conditioin of presence of wind, the wind speed and ambient temperature can meet the requirements of heart preservation,it is found that the shaped parts should be paid attention to the proper distance of branch pipe in the heat insulation construction, otherwise it will cause a large amount of heat loss.