Analysis on the Development & Application of Heat Exchanger with Cooper Fin Part Ⅱ:Influence of Heat Exchanger with Cooper Fin on the Performance of Air Conditioner

刘建,丁国良,吴志刚,高屹峰
DOI: https://doi.org/10.3969/j.issn.2095-3429.2004.05.003
2004-01-01
Abstract:Based on the analysis of the fin efficiency, total heat transfer conductivity and heat transfer capacity with copper fin in Part I, the influence of heat exchanger with copper fin on the performance of air conditioner is further studied theoretically. It shows that coefficient of performance (COP) of air conditioning system could be improved when using the copper fin instead of aluminum fin, and the influence of evaporator with copper fin is greater than that of condenser. When the enhanced factor of heat conductivity is 1.1, the value of COP can be improved 3.0%-10.0%, while the enhanced factor of heat conductivity is 1.3, the corresponding value of COP can be improved 4.0%-25.0%. The feasibility analysis on the development application of heat exchanger with copper fin provides a guideingline to developing the high performance and small size residential air conditioner.