Effects of water mal-distribution on thermostatic-expansion-valve stability

Dong HUANG,Yongqiang LENG,Zhenya ZHANG
DOI: https://doi.org/10.11918/j.issn.0367-6234.201603101
2017-01-01
Abstract:To explore the hunting behavior of the thermostatic-expansion-valve ( TEV) , dynamic characteristics of the TEV ( TEX2 externally balanced type ) control-loop ranged from stability to vibration were studied under the selected 7 sets of water mal-distribution experimentally. Results showed that as F2 dropped from 36.9% to 27.0%, the TEV control-loop was stable and the overall evaporator capacity decreased by only 3.4%. As F2 dropped from 27. 0% to 9. 1%, evaporator overall outlet temperature changed from stability to vibration. Its vibration amplitude increased gradually with the phase transformation from vapor to mist, indicating that hunting behavior of TEV control-loop occurred, and the overall evaporator capacity decreased by 14. 1%. The superheated refrigerant gas from Circuit 1 outlet only provided sensible heat and couldn' t evaporate the liquid refrigerant out of Circuit 2 into superheated steam. Consequently, refrigerant in the evaporator overall outlet was of a smaller superheat than the necessary minimal stable signal ( MSS) of the TEV, even at two-phase state, and would inevitably give rise to the hunting of the TEV-controlled system according to the MSS theory. These experimental results might provide references for the design of the heat exchanger of multi-circuit refrigerating system.