Research and Application of Sub-synchronous Harmonic Monitoring System for Wind Farm

姚秀萍,薛忠,郭小龙,王衡,常喜强,王维庆,李自明
DOI: https://doi.org/10.3969/j.issn.0559-9342.2017.05.021
2017-01-01
Abstract:In view of the sub-synchronous oscillation problem of wind power generation in UHV DC transmission system,the synchronous devices in wind farm,converter station and other related sites of wind power collection areas are incorporated into monitoring system based on synchronized Phasor Measurement Unit (PMU) tool.The sub-synchronous oscillation is judged by detecting the active power oscillation waveform of tie line and combining with the sub-synchronous harmonic frequency characteristics of contact line.To a specific disturbance,the data spectrum recorded by PMU in monitoring system show that the monitoring and recording results of sub-synchronous harmonics monitoring device and other torsion vibration monitoring protection device are basically same in processing and disturbance wave form.