STUDY OF THE MULTIPLE VARIABLES FUZZY CONTROL ON THERMAL AND HUMIDITY CONDITIONS

Jianli Zhang,Hongfeng Zhou,Jin Zhang,Hui Zhang,Maoting He,Tian Bai,Le Yuan
2009-01-01
Abstract:Thermal performance of fresh air ventilator could be evaluated accurately by two room method, and control precision of temperature and humidity conditions in room A and room B impacts greatly on the accuracy of the results of the assessment. Two rooms air system is a typical multi-variable, big lag, temperature and humidity coupled system. Traditional PID control is difficult to achieve high-precision control of temperature and humidity conditions. In response to these issues, this paper solves the problem of this type of multi-variable control, by the method of a combination of the traditional PI control and fuzzy control. This paper brings forward the control system design, establishes rules of fuzzy control and query table of fuzzy control based on experiment and air-conditioning theory, makes a great deal of testing and parameters adjustment and obtain better control. The control precision of temperature of two rooms can be up to +/- 0.2 degrees C, the control precision of the relative humidity of two rooms up to +/- 1.5%. Thermal performance test of fresh air ventilator with two rooms can be fully met.
What problem does this paper attempt to address?