Study on Aging Characteristics of MOV in Energy Absorption Branch of Hybrid DC Circuit Breaker

Wang Xinyi,Liu Yiying,Yu Penghao,Li Weikang,Wang Hao
DOI: https://doi.org/10.1109/icemi46757.2019.9101485
2019-01-01
Abstract:With the development of power electronics technology, the hybrid DC circuit breaker (HDCCB) consisting of mechanical switches, semiconductor devices and metal oxide varistor has been intensively studied. As an important component to protect HDCCB, the energy absorption of MOV is an important parameter affecting the development of DC grid protection. At present, the research on HDCCB mostly ignores the effectiveness of MOV protection performance. In this paper, we have carried out an accelerated aging experiment on the MOV in HDCCB's energy absorption branch, in order to explore the aging effect of the operating overcurrent wave generated by breaking short-circuit current on the MOV. The experiment results show that the operating overcurrent wave causes perforation damage to the MOV. Before the damage occurred, the MOV did not reach the aging standard. This study provides an experimental basis for the evaluation of MOV aging life in HDCCB.
What problem does this paper attempt to address?