Single-phase Adaptive Reclosure Scheme Using Impedance Property of Fault Loop in Shunt-reactored Transmission Lines

Pengyue Liu,Wenquan Shao,Guobing Song
DOI: https://doi.org/10.1109/APAP47170.2019.9224891
2019-01-01
Abstract:In AC/DC hybrid system, unsuccessful auto-reclosing in single-phase faults in AC side may cause continuous commutation failure, an adaptive single-phase reclosure scheme is proposed using the impedance property of the fault loop in transmission lines. The impedance is determined by the terminal-voltage of the fault phase and current of the ground capacitance. In transient faults with extinguished arc, the impedance is mainly determined by the ground capacitance of the fault phase. In permanent faults, it is mainly determined by the ground capacitance of the fault phase and transition resistance, which distincts from transient faults. The results show that the scheme is unaffected by fault location, line compensation and transition resistance and it is suitable for transmission lines with shunt reactors at one or both terminals.
What problem does this paper attempt to address?