WIDE-AREA REAL TIME DYNAMIC SECURITY MONITORING SYSTEM OF NORTH CHINA POWER GRID
李丹,韩福坤,郭子明,张黎,吕少坤,魏小伟,田枚,张雪轩,刘长银,肖晋宇,谢小荣,吴京涛,王立鼎,杨东,肖晓春
DOI: https://doi.org/10.3321/j.issn:1000-3673.2004.23.011
2004-01-01
Abstract:The full view of power system dynamic processes can be supervised by wide-area real time dynamic monitoring system (WAMS) based on synchronous phasor measurement (SPM) technology. Meanwhile, the recorded data of the power system disturbance accidents is helpful to the off-line verification of the model and parameters of simulation system. Based on the development of real-time dynamic monitoring system for North China Power Grid, the architecture, main functions and features of the monitoring system are described in detail. The first stage of this monitoring system consists of the master-station located at the dispatching center of North China Power Grid and the sub-stations installed in seven key power plants and substations; the connection among the sub-stations is implemented by dispatching data network. The practical application of this WAMS in North China Power Grid is presented through the artificial large disturbance test for three-phase short circuit occurred in Northeast China Power Grid.