ANALYSIS OF EMI DUE TO GROUNDING CURRENT IN A PWM INVERTER-INDUCTION MOTOR DRIVE SYSTEM

陈斌,姜建国,孙旭东
DOI: https://doi.org/10.3321/j.issn:0258-8013.2003.02.013
2003-01-01
Abstract:In IGBT PWM inverter - induction motor system, the high |dv/dt| and |di/dt| due to the fast switching of IGBT could bring serious EMI issues. Research shows that, in order to characterize the EMI issue, it is important not only to know its waveform in time domain but also to investigate its spectra. This paper uses a novel approach adopting a linear system function to characterize the EMI generation and coupling avoiding complicated parameter extraction of the parasitic circuit. The highest grounding current pike appears when the |dv/dt| is the highest. There is hardly a variance of the |dv/dt| at turn-on over a wide load current range, however, the lower the load current, the lower the |dv/dt| at turn-off. The grounding current EMI issue is mainly dominated by the turn-on of IGBTs because the |dv/dt| at turn-on is much higher than that at turn-off. The amplitude-frequency characteristic of the system function of coupling path appears as band-pass, and with small deviation, the legs of a three-phase inverter could be considered as almost three equal contributors to grounding current noise. Although the inverter's topology construction alternates while it works, it hardly has affect to this system function. The current may double when two IGBTs of three legs turn on/off almost at the same time.
What problem does this paper attempt to address?