Spectroscopic study on relationship between contacts erosion and chromatic parameters of arc in a HVCB

Zhixiang Wang,Gordon R. Jones,Joseph W. Spencer,Xiaohua Wang,Mingzhe Rong
2016-01-01
Abstract:Contacts erosion is one of the most crucial factor affecting the electrical service lifetime of high-voltage circuit breakers (HVCBs). Monitoring the contacts’ erosion degree is increasingly in demand for the sake of condition based maintenance to guarantee the functional operation of HVCBs. An experimental test rig has been designed based upon a commercial 245kV/40kA SF6 puffer type circuit breaker with copper-tungsten (28%wt and 72%wt) arcing contacts under atmospheric pressure. Three optical-fibre based sensors are used to capture the time-resolved spectra of arcs. A novel approach using chromatic methods to process the time-resolved spectral signal has been proposed. The processed chromatic parameters have been interpreted to show that the time variation of spectral emission from the contact material and quenching gas are closely correlated to the mass loss and surface degradation of the plug arcing contact. The feasibility of applying this method to on-line monitoring of contact erosion is indicated.
What problem does this paper attempt to address?