Effect of atmospheric conditions on cable termination to switchgear

Abdur Rashid,Asmatullah Khan,S. F Shaukat
2008-01-01
Abstract:ABSTRACT: An intensive research work is carried out to determine the effect of humidity and contamination on cable termination and it’s aging. In this paper, the effect of atmospheric conditions on cable termination has been investigated by measurement of discharge inception voltage, discharge magnitude, dielectric loss and capacitance of each phase of cable. The three possible conditions i.e normal, wet and contaminated have been simulated in the laboratory. The deterioration is determined under simultaneous stress from applied voltage and contamination by measuring various parameters. It can be stated with some confidence that above mentioned factor under these conditions will help to know about the conditions of termination and aging of the cable. The cable was three phase Aluminum core XLPE cable and connected to switchgear through an epoxy resin bushing. Termination was made by heat shrinkable method.
What problem does this paper attempt to address?